LG P05AH-NTO Floor Standing Heat Pump (13.50 Kw / 45000 Btu) Fixed Speed

SAVE OVER 55%!!!!!!!

An efficient, stylish and brilliantly engineered system that provides perfect temperature control for large spaces such as warehouses, large open plan offices and retail units

Click to enquire

LIMITED STOCK - GET IN TOUCH NOW TO AVOID DISAPPOINTMENT!

Floor / Ceiling feature's

The Floor standing System is designed to exchange air quickly with a high speed centrifugal fan. The Indoor Unit can easily be mounted on the floor of fixed to a wall. The System features Gold Fin protection on the Outdoor Unit & Energy Saving Plasma Heat Exchanger in the Indoor Unit.
Heating / cooling / dehumidification

Airflow Direction Control
Horizontal Airflow Direction Control. Adjust the horizontal airflow direction by manually moving the horizontal airflow direction louver by hand.
  
Vertical Airflow Direction Control. The airflow direction can be adjusted as desired by using the remote controller.
  
Gold FinTM Anti Corrosion
LG’s Outdoor Heat Exchanger is coated with a golden anti-corrosive epoxy treatment on the aluminum coil to minimised corrosion. This maintains heat transfer properties of the coil for an extended time where as non-Gold Fin coils progressively lose efficiency due to surface corrosion. Standard on every LG air conditioner, this assists in areas suffering from pollution or near the ocean where the unit may subjected to higher levels of salt.

Super Low Power Consumption Use in Standby Mode by Adopting SMPS
(Switching Mode Power Supply)
Power waste due to standby power - Power is wasted if a plug is connected to an outlet even though the appliance is turned off. Development of super power-saving SMPS (Switching Mode Power Supply) - Low standby power function reducing standby power by 90%

Product Key Feature's
• Plasma Air Purifying System
• Anti Corrosion Gold Fin (Outdoor)
• Weekly Program
• Low Standby Power
• Child Lock Function
• Easy-to-Clean Air Filter
• Optimal Air Distribution
• Auto Cleaning
• Auto Changeover
• Auto Restart
• Auto Operation
• Quiet Operation
• Healthy Dehumidification
• Hot Start
• 24-Hour ON/OFF Setting Timer
 
• Optimal air distribution with directional Air flow system
 

Technical Specification

Nominal Capacity Cooling     kW  -    13.50  

Capacity (UK) Cooling     kW  -  12.65  

Nominal Capacity (T1) Heating     kW  -   14.10

Power Supply to Unit     V/Phase/Hz  -  415/3/50      

Power supply to  -   Outdoor      415/3/50 (3 PHASE)

Inter connecting Cables   -  4      

cores and rating     No. Amps      5

Running Current     Cooling     Amps  -   9.5

Running Current     Heating     Amps   -  9.0   

Power Input     Cooling     kW  -  5.3

Power Input     Heating     kW  -  5.0      

Start Current     Cooling     Amps     -     6.0

Start Current     Heating     Amps     -     6.0

Circuit Breaker     Amps   -  20      

T1 EER     Cool     (W/W)   -  2.91

T1 COP     Heat     (W/W)  -   2.91     

ECA compliant    -   yes     

Air Circulation     Indoor  -   (m3/min)   -  30

(High Speed)     Outdoor  -   (m3/min)  -   35      

Sound Levels     Indoor  -   dB(A)+/-3 (at 1.0m)  -   32

(High Speed)     Outdoor   -  dB(A)+/-3 (at 1.0m)  -   49      

Indoor Units     WxHxD     (mm)  -   570 x 1820 x 317

Outdoor Units     WxHxD     (mm)  -   900 x 1165 x 370      

Indoor Units     (Kg)  -   33      

Outdoor Units     (Kg)  -  90      

Liquid     (Inch)   -  3/8      

Suction     (Inch)   -  3/4      

Drain (ID)     (mm)   - 32      

Maximum Elevation     (m)  -   7      

Max. Distance between In & Out     (m)  -  3 - 40      

Factory charge     (Kg)  -   2.9      

Charged for — m     (m)  -   7.5      

Additional g/m     (g/m) -    40