LG UT36H.NM1/UU36WH.U31 10kw 36,000btu Heat Pump H Inverter Ceiling Cassette System
The LG Ceiling Cassette range comes with wide jet air flow, independent vane operation, BLDC compressor, streamlined airflow and extremely quiet operation.
Model Indoor Unit | UT36H.NM1 |
Fascia Panel | PT-UMC1 |
Cooling Capacity Min~Rated~Max kW | 4.50~10.00~13.00 |
Heating Capacity Min~Rated~Max kW | 4.90~11.20~14.00 |
Power Input Cooling (Rated~Max) kW | 2.60 ~ 4.42 |
Heating (Rated~Max) kW | 2.51 ~ 4.60 |
EER W/W | 3.85 |
COP W/W | 4.46 |
SEER | 5.61 |
SCOP | 4.11 |
PdesignH (@-10°C) kW | 11.3 |
Energy Efficiency Class Cooling/Heating W | A+/A+ |
Annual energy consumption Cooling kWh | 1300 |
Power Supply Ø / V / Hz | 1 / 220-240 / 50 |
Air Flow Rate Indoor, H/M/L m3/min | 32 / 26.1 / 20.2 |
Sound Level Indoor, H/M/L dB(A)±3 | 47 / 45 / 42 |
Operation Range Cooling (Indoor) °C | 18~30 |
Cooling (Outdoor) °C | -10~48 |
Heating (Indoor) °C | 16~30 |
Heating (Outdoor) °C | -18~18 |
Running Current Cooling/Heating A | 0.72 / 0.72 |
Power Supply to... | Outdoor |
Moisture Removal Rate l/h | 2.7 |
Drain Hose (O.D / I.D.) mm | 32 / 25 |
Dimensions Indoor (WxHxD) mm | 840x288x840 |
Fascia (WxHxD) mm | 950x25x950 |
Net Weight Indoor kg | 28 |
Fascia kg | 5 |
Model Outdoor Unit | UU36WH.U31 |
Power Supply Ø / V / Hz | 1 / 220-240 / 50 |
Running Current Cooling/Heating A | 11.5 / 11.3 |
Starting Current Cooling/Heating A | < 11.5 / 11.3 |
Suggested Circuit Breaker Type C A | 25 |
Power Supply to... | Outdoor |
Interconnecting Cable | 3-Core + Earth |
Compressor Type | Twin Rotary |
Air Flow Rate Outdoor, Max m3/min | 55 x2 |
Sound Level Cooling/Heating dB(A)±3 | 51 / 53 |
Night Operation dB(A)±3 | 47 |
Dimensions Outdoor (WxHxD) mm | 950x1380x330 |
Net Weight Outdoor kg | 103 |
Refrigerant & Charge R410A g | 3600 |
Additional Refrigerant charge g/m | 40 (>7.5m) |
Piping Connections Liquid Side mm (in) | 9.52 (3/8) |
Gas Side mm (in) | 15.88 (5/8) |
Piping Length (Min/Max) m | 5 / 75 |
Max. Elevation Difference m | 30 |