LG UV36H.NL1/UU36WH.U31 10kw 36,000btu Heat Pump H Inverter Ceiling Suspended System

The LG CEILING SUSPENDED range comes with airflow direction control, precise temperature reading and the option of a wired remote controller.






Click to enquire

 

 

 

 

 

 

 

Model Indoor Unit UV36H.NL1
   
Cooling Capacity Min~Rated~Max kW 4.30~10.00~12.40
Heating Capacity Min~Rated~Max kW 4.20~10.50~13.70
Power Input Cooling (Rated~Max) kW 2.77 ~ 4.16
Heating (Rated~Max) kW 2.62 ~ 4.70
EER W/W 3.61
COP W/W 4.01
SEER 5.61
SCOP 4.11
PdesignH (@-10°C) kW 11.3
Energy Label Cooling/Heating A+ / A+
Annual Energy Consumption Cooling/Heating kWh 1385
Power Supply Ø / V / Hz 1 / 220-240 / 50
Air Flow Rate Indoor, H/M/L m3/min 28.6 / 26.9 / 25.2
Sound Pressure Level Indoor, H/M/L dB(A)±3 46 / 44 / 43
Operation Range Cooling (Indoor) °C 18~30
Cooling (Outdoor) °C -10~48
Heating (Indoor) °C 16~30
Heating (Outdoor) °C -18~18
Running Current Cooling/Heating A 0.90 / 0.90
Power Supply to... Outdoor
Moisture Removal Rate l/h 2.93
Drain Hose (O.D / I.D.) mm 20 / 16
Dimensions Indoor (WxHxD) mm 1750×650×220
Net Weight Indoor kg 45
   
Model Outdoor Unit UU36WH.U31
   
Power Supply Ø / V / Hz 1 / 220-240 / 50
Running Current Cooling/Heating A 11.5 / 11.3
Starting Current Cooling/Heating A < 11.5 / 11.3
Suggested Circuit Breaker Type C A 25
Power Supply to... Outdoor
Interconnecting Cable 3-Core + Earth
Compressor Type Twin Rotary
Air Flow Rate Outdoor, Max m3/min 55 x2
Sound Level Cooling/Heating dB(A)±3 51 / 53
Night Operation dB(A)±3 47
Dimensions Outdoor (WxHxD) mm 950x1380x330
Net Weight Outdoor kg 103
Refrigerant & Charge R410A g 3600
Additional Refrigerant charge g/m 40 (>7.5m)
Piping Connections Liquid Side mm (in) 9.52 (3/8)
Gas Side mm (in) 15.88 (5/8)
Piping Length (Min/Max) m (5/75)
Max. Elevation Difference m 30